The Influence of Water and Straw Powders Contaminants on Shell Diala B Transformator Oil

Closed

Moch. Dhofir, Rini Nur Hasanah, Hadi Suyono, Hesti Vini Widiastuti, Lestari Ayuningsih, Hery Purnomo

2018 ICHVE 2018 - 2018 IEEE International Conference on High Voltage Engineering and Application Conference paper Cited by 5 Quartile

Abstract

The presence of water and straw powders contaminants even at a relatively small amount may decrease the breakdown voltage and increase the leakage current of the shell diala B transformer oil significantly. The polarization of water and straw powders contaminants in the electric field causes the formation of conductive bridges between the anode and cathode. The breakdown voltage and leakage current in a homogeneous field distribution are greater than those in the nonhomogeneous field. © 2018 IEEE.